Voltage Drop
Voltage drop and wire size calculator for DC, single and three phase
Voltage Drop works out the voltage lost along a run of wire, the voltage left at the load and the power lost in the wires, and the smallest wire size, the longest run or the most current that keeps the drop within your limit. It works each conductor’s resistance from its size and the physics of copper and aluminium, can add AC reactance from the conductors’ spacing, and shows every step of the arithmetic. It works offline, has no account, no ads and no subscription.
Get it on Google PlayWhat it does
- Voltage drop in volts and percent, the voltage at the load and the power lost in the wires, for DC, single-phase AC and three-phase AC
- The smallest wire size that keeps the drop within your limit, with what the size below it would drop
- The longest run for a size and the most current for a size and length, rounded down so the figure shown keeps within the limit
- Copper or aluminium, AWG 18 to 4/0 and kcmil 250 to 1000 or 1.5 to 400 mm², up to ten sets in parallel, feet or metres
- Resistance worked from the wire’s size, the resistivity and temperature coefficient of the metal and a stated stranding allowance, at a conductor temperature you set
- Optional AC reactance from the conductors’ spacing, with skin effect, at the power factor you enter, at 60 or 50 Hz
- Every size side by side for your circuit, with the ones within your limit marked
- Every step of the working shown under each answer, and any result shared as plain text
- Circuits saved on your phone, light and dark screens, and nothing collected
Questions
How does the app work out a wire’s resistance?
From the physics, not from a code book’s table. It takes the wire’s cross-section (from the AWG diameter formula, the kcmil or the mm²), the resistivity of copper or aluminium at 20 °C and how it rises with temperature, and adds 2% for stranding unless you change it. For AWG and kcmil sizes the figures agree with published US conductor tables within about 1%. Metric sizes are worked from their nominal area: the international conductor standard limits a cable’s resistance rather than its area, and allows up to about 13% more than the nominal area gives, so compare with your cable’s data sheet if you are close to your limit.
Why doesn’t it tell me the ampacity?
Ampacity comes from your electrical code’s tables and depends on the insulation, the temperature rating, the terminations, how many wires are together and the surroundings. The app works out voltage drop only. Wherever it suggests a size or a current, check the ampacity, the overcurrent protection and the rest of the circuit against your local code: a wire that keeps within a voltage drop limit can still be too small for its load.
Which length do I enter?
The one-way length, from the source to the load. For DC and single-phase circuits the current goes out and comes back, so the app counts twice the length of wire; for a balanced three-phase circuit it uses √3. The working shows which.
What is the difference between the resistive drop and the drop with reactance?
Left as it is, the app gives the resistive drop: the current times the wires’ DC resistance, the usual quick method. On AC, conductors also have reactance, and large conductors (from about 1/0 AWG or 70 mm²) feeding a load with a lagging power factor drop noticeably more than the resistive figure. Turn on reactance to include it: the app works out each conductor’s reactance from the spacing between conductors and adds the skin effect, at the power factor you enter. For small wires at a low power factor the drop with reactance can come out lower than the resistive drop, because the current is partly out of step with the voltage.
What limit should I use?
US code books recommend, but do not require, no more than 3% on a branch circuit or a feeder and 5% for both together. Other countries’ rules set their own figures, often 3% for lighting and 5% for other uses. Your job’s specification or your local code may set its own: use the limit that applies to your work.
Does it work for DC, solar and battery circuits?
Yes, for any two-wire DC circuit up to 1,500 V: enter the voltage, the current and the one-way length. On low-voltage DC, such as 12 V, a few tenths of a volt is already several percent, so the size finder is useful there.
Can I run conductors in parallel?
Yes: set the number of sets, and the app shares the current equally between them. Parallel conductors must be the same size, metal, length and type and be joined the same way at both ends, and codes usually allow them only for large sizes. Check yours.
Is it safe to rely on the numbers?
Check them. The app is a calculating aid, not the electrical code, and not a substitute for the inspector or a qualified electrician. Its results are estimates that depend on what you enter. Work on circuits only if you are qualified to, with the power off and locked out, and have the work inspected where the law requires it. The app comes with no warranty.
Does the app collect anything?
No. It has no internet access, no account, no ads and no analytics. Your circuits stay on your phone.